Skip to content

BTC

  • Heating cable for freeze protection and temperature maintenance
  • 120°C: maximum tolerance temperature with powered cable
  • Automatically varies power output as temperature changes
  • For freeze protection and temperature maintenance in industrial applications
  • Does not produce dangerous overheating or deterioration even when overlaid

BTC

Notes on operation:

  • Maximum tolerance temperature with powered cable 120°C and unpowered 200°C
  • Minimum installation temperature: -30°C
  • Minimum operating temperature: -60°C
  • Power supply voltage: 220-240 V a.c.
  • W/m available: 15, 30, 45, 60

Examples of application:

  • Freeze protection and industrial process applications with temperatures up to 120°C
  • Ideal solution for keeping particularly critical substances at temperature

Temperature classes:
15, 30, 45 e 60 W/m
T3 (200°C)
Model Nominal dimensions (mm) Minimum bending radius Safe zone cable gland ATEX cable gland
BTC BP 12,8 x 5,7 25mm - M25

BTC BP

Version with metal mechanical protection sleeve and earthing braid and subsequent fluoropolymer coating. For use in the presence of highly corrosive elements.

 

Maximum circuit length in metres depending on the size of the circuit breaker used and 230V ac power supply:

 

ModelStarting temperature 10A 16A 20A 32A
15BTC10°C120165200220
0°C115155179210
'-20°C100145158200
'-40°C90125139178
30BTC10°C85115120135
0°C80110120130
'-20°C70100105125
'-40°C639095105
45BTC10°C558085100
0°C50808298
'-20°C45757795
'-40°C42656785
60BTC10°C45707385
0°C42687080
'-20°C39636578
'-40°C35555870

With differential circuit breaker protection 30 mA curve C according to IEC60898

The BTC cable is a self-regulating semi-conductive matrix heating cable used for freeze protection and for industrial process applications with temperatures up to 120°C. Its self-regulating characteristics make it very reliable and safe. It also does not produce overheating or burning, even when overlaid. It is the ideal solution for keeping particularly critical substances at temperature.

BTC heating cable can be cut to length on site to the required length of the pipes, valves, pumps on which it is to be installed. It can be spliced and branched in parallel with extreme ease of design and installation and it is not necessary to know the exact layout of the system when ordering. No special equipment is required for its installation and it is secured to pipes with simple adhesive tape. The kits include supply-side and terminal-side terminations and cable glands for connecting the heating cable directly into the power supply box.

 

emperature curve:

The graph shows the power rating supplied with a 230 V ac power supply and the cable installed on a suitably insulated metal pipe and dimensioned according to standards IEC 62395 and IEC 60079-30.

Certifications

Request an Online Quote now

For more information on our products and areas of application, please do not hesitate to contact us, we will provide you with all the details you need.