Model | Nominal dimensions (mm) | Minimum bending radius | Safe zone cable gland | ATEX cable gland |
---|---|---|---|---|
FSR CT | 12,95 x 5,95 | 35mm | M25 | M20 |
FSR CF | 12,95 x 5,95 | 35mm | M25 | M20 |
FSR CT
Version with metal mechanical protection sleeve and earthing braid and subsequent thermoplastic coating. For use in explosion-proof zones.
FSR CF
Version with metal mechanical protection sleeve and earthing braid and subsequent fluoropolymer coating. For use in explosion-proof zones or in the presence of highly corrosive elements.
Maximum circuit length in metres depending on the size of the circuit breaker used and 230V ac power supply:
Model | Starting temperature | 10A | 16A | 20A | 32A |
10FSR | 10°C | 136 | 198 | 198 | 198 |
0°C | 122 | 188 | 188 | 188 | |
'-20°C | 108 | 174 | 176 | 176 | |
'-40°C | 96 | 154 | 166 | 166 | |
17FSR | 10°C | 92 | 148 | 154 | 152 |
0°C | 84 | 134 | 144 | 144 | |
'-20°C | 74 | 118 | 136 | 136 | |
'-40°C | 66 | 106 | 128 | 128 | |
25FSR | 10°C | 74 | 118 | 124 | 124 |
0°C | 68 | 108 | 120 | 120 | |
'-20°C | 60 | 96 | 112 | 112 | |
'-40°C | 52 | 84 | 106 | 106 | |
31FSR | 10°C | 58 | 92 | 112 | 112 |
0°C | 52 | 84 | 104 | 106 | |
'-20°C | 46 | 74 | 92 | 100 | |
'-40°C | 42 | 66 | 82 | 94 | |
40FSR | 10°C | 46 | 74 | 92 | 98 |
0°C | 42 | 66 | 84 | 94 | |
'-20°C | 36 | 58 | 74 | 88 | |
'-40°C | 32 | 52 | 66 | 84 |
With differential circuit breaker protection 30 mA curve C according to IEC60898