Model | Nominal dimensions (mm) | Minimum bending radius | Safe zone cable gland | ATEX cable gland |
---|---|---|---|---|
FSU NF | 12,1 x 5,4 | 35mm | M25 | M20 |
FSUw NF | 14,4 x 5,6 | 35mm | M25 | M25 |
FSU N
Version with metal mechanical protection sleeve and earthing braid for explosion-proof zones
FSU(w) NF
Version with metal mechanical protection sleeve and earthing braid and subsequent fluoropolymer coating for explosion-proof zones and in the presence of highly corrosive vapours and solutions.
Maximum circuit length in metres depending on the size of the circuit breaker used and 230V ac power supply:
Model | Starting temperature | 10A | 16A | 20A | 32A | 50A |
15FSU | 10°C | 76 | 122 | 154 | 172 | 172 |
0°C | 70 | 112 | 140 | 172 | 172 | |
'-20°C | 62 | 98 | 122 | 172 | 172 | |
'-40°C | 52 | 82 | 102 | 164 | 172 | |
30FSU | 10°C | 52 | 82 | 102 | 122 | 122 |
0°C | 46 | 74 | 92 | 122 | 122 | |
'-20°C | 40 | 66 | 82 | 122 | 122 | |
'-40°C | 34 | 54 | 68 | 110 | 122 | |
45FSU | 10°C | 38 | 62 | 76 | 100 | 100 |
0°C | 34 | 56 | 70 | 100 | 100 | |
'-20°C | 30 | 50 | 62 | 98 | 100 | |
'-40°C | 22 | 34 | 44 | 70 | 100 | |
60FSU | 10°C | 30 | 50 | 62 | 86 | 86 |
0°C | 28 | 44 | 56 | 86 | 86 | |
'-20°C | 20 | 32 | 40 | 62 | 86 | |
'-40°C | 12 | 18 | 24 | 38 | 60 | |
75FSU | 10°C | 22 | 34 | 44 | 70 | 76 |
0°C | 16 | 26 | 34 | 54 | 76 | |
'-20°C | 12 | 18 | 24 | 38 | 60 | |
'-40°C | 8 | 12 | 14 | 22 | 36 |
With differential circuit breaker protection 30 mA curve C according to IEC60898
FAILSAFE FSU is a self-regulating heating cable with semi-conductive matrix suitable for high operating temperatures up to 250°C.
Its inherent ability to self-limit its temperature to a value below the maximum allowed by the materials used in its construction allows it to be used without any need for thermostatic control. Furthermore, the cable is manufactured using FAILSAFE technology and does not produce power at its maximum operating temperature.
For this reason, the maximum operating temperature is the same whether the cable is powered or not. Installation is quick and easy as it can be cut, branched and terminated to size directly on site without the need for special equipment.
Temperature curve:
The graph shows the power rating supplied with a 230 V ac power supply and the cable installed on a suitably insulated metal pipe and dimensioned according to standards IEC 62395 and IEC 60079-30.
For more information on our products and areas of application, please do not hesitate to contact us, we will provide you with all the details you need.